Certification Record |
|
| CUSTOMER |
CLASS |
FILE |
|
| ABB STOTZ-KONTAKT GmbH |
3215-30 |
098793_0_000 |
| Eppelheimer Strasse 82, |
SUPPLEMENTARY PROTECTORS-COMPONENT ACCEPTANCE PROGRAM |
|
| Heidelberg |
| Baden-Wurttemberg |
| 69123 |
|
|
| Germany |
Refer to Class Description for program details |
- Series S210, Types S211-S214, K or Z or UCK.
- Series S250, Cat. Nos. S251, S252, S253, with suffix L.
- Series S163, Types S163-G10, S163-G14.
- Accessories for Supplementary Protectors series S 280, S 270 and S 250
- Series S280, Types S281X3B16NA, S281X3B32NA, S283B32NA.
- Series S220, Cat. Nos. S221, S222, S223 and S224 with suffix K.
- Component Supplementary Protectors Series S280, Cat. Nos. S281, S282, S283 and S284
followed by DS, K, L, Z, UCK or UCZ followed by a number between .02 and 63. All catalogue
numbers may have suffix NA. Series S260, Cat. Nos. S261, S262, S263 and S264 followed by a
number between 320 and 63. All catalogue numbers may have suffix NA.
These devices are one pole protectors that may be ganged together to form a multipole
device (4 poles maximum). When ganged together a common trip lever is used between poles.
The 1, 2, 3 and 4 following S26 or S28 stands for the number of poles. The letters in the
catalogue number following the number of poles stands for the trip curve. The UC in the
catalogue number means it has both ac and dc ratings. The last digits stand for the ampere
rating.
RATINGS:
Current Ratings:
S280 Series the maximum rating is 63A
S260 has a minimum rating of 32A and a maximum rating of 63A.
S260-B has a minimum rating of 6A and a maximum rating of 63A.
S260-C has a minimum rating of 0.5A and a maximum rating of 63A.
S260-D has a minimum rating of 0.5A and a maximum rating of 63A.
Voltage Ratings:
S281 K, Z are rated 277V ac maximum.
S282 K, Z are rated 480V ac maximum.
S273, S263, S264, S283, S274 and S284 K, L, Z, UCK and UCZ are rated 480V ac maxium.
S281 UCK and UCZ are rated 277V ac, 250V dc maximum.
S282, S283, S284 UCK and UCZ are rated 400V ac, 500V dc maximum.
S261 are rated 277V ac, 60V dc.
S262, S263 and S264 are rated 480V ac, 125V dc (two poles in series).
Short Circuit Ratings -
S260 Series followed by D: 6kA/277V ac single pole 6kA/480V, 10kA rms symmetrical 120V
ac, 60V dc, one pole, 240V ac, 125V dc multipole.
S280 Series followed by UCK or UCZ: all devices 4.5kA or dc. Devices rated 40A or less
6kA/240V. Devices rated greater than 40A - 5kA/277V ac for single pole 5kA/480V ac for
multipole.
S280 Series followed by K or Z: single pole - devices rated 40A, or less - 10kA/277V
ac, devices rated greater than 40A - 6kA/277V ac. Multipole: devices rated 32A or less -
10kA/480V ac, devices rated greater than 32A - 6kA, 480V ac.
Application Codes: See Product Application Codes Table.
Notes:
- These devices are intended to be rail mounted and should be mounted in a non-metallic
enclosure or in a metallic enclosure having an insulator under the mounting wall.
- The terminals of the device have not been investigated for field wiring.
- These devices are not suitable for branch circuit protection.
- Short circuit Tests on the S280 protectors were conducted without series protection.
- For use only in products where the acceptability of the combination is determined by CSA
International.
- Types S260 were subjected to Short Circuit Tests with series fuses rated 4 times the
ampere rating of the protector. 6kA and 10kA short circuit tests with 277V ac and 480V ac
on type S280 were conducted with series fuses rated 4 times the ampere rating of the
protector.
- The spacings from live parts of single pole devices to adjacent metal surfaces, and from
the outside poles of multipole devices to adjacent metal surface shall be evaluated in the
end product application.
- Temperature Test on S260 was performed in an enclosure approx 157 mm by 59 mm by 68 mm.
- Component Supplementary Protectors Series S280, Cat. Nos. S271, S272, S273 and S274
followed by letters K, KS or Z followed by a number between .5 and 63 may be followed by
additional suffixes. All catalogue numbers may have suffix NA.
These devices are one, two, three and four pole supplementary protectors provided with
thermal magnetic trip units. Devices may or may not be provided with auxiliary switches.
The 1, 2 or 3 following S26 or S27 stands for the number of poles. Poles with NA suffix
have switch neutral pole with no trip.
RATINGS:
Current Ratings:
S270-K or Z ratings minimum 0.5A maximum 63A
Voltage Ratings:
One pole devices - 277V ac
Multipole devices - 480V ac (2 poles breaking
Short Circuit Ratings:
6kA rms symmetrical 277V ac, one pole, 480V ac multipole
10kA rms symmetrical 120V ac, 60V dc, one pole, 240V ac
125V dc multipole
Additional Ratings:
Temperature -25C to 25C (S260
Temperature -25C to 55C (S270
S280-K is suitable for across-the-line motor starting ac and may have hp ratings as
indicated under "Markings".
Application Codes: See Product Application Codes Table.
Notes:
- These devices are intended to be rail mounted.
- The terminals of the device have not been investigated for field wiring.
- These devices are not suitable for branch circuit protection.
- Short circuit tests on the following types of protectors were conducted without series
protection. S270-K rated 0.5-40A and 110V dc or 240V ac (multipole); or 60V dc (1 pole).
- The spacing provided between adjacent terminals on multipole devices when the devices
are used in pollution degree 2 environments and overvoltage category 3 or better.
- The spacings from live parts of single pole devices to adjacent metal surfaces, and from
the outside poles of multipole devices to adjacent metal surface shall be evaluated in the
end product application.
- The temperature test for devices suitable for 25C ambient was performed in an enclosure
measuring approx 157 mm by 59 mm by 68 mm.
- Short circuit tests for 10kA rating were conducted without series protection.
- For use only in products where the acceptability of the combination is determined by CSA
International.
- Component supplementary protector accessory, auxiliary contact S2-H, S3-H and S2-S/H.
These devices are auxiliary contacts intended for use with this manufacturer's
supplementary protectors, S280, S270 and S250. Auxiliary contacts operate off the
protector main contact mechanism. The signal contact on the S2-S/H operates off the
protector trip mechanism.
Ratings:
| S2-S/H |
.5A, 250V dc |
2A, 415V ac |
|
1A, 110V dc |
6A, 240V ac |
|
4A, 24V dc |
|
| S2H and S3-4 |
2A, 60V dc |
6A, 240V ac |
Notes:
- These devices are intended for rail mounting and used in conjunction with supplementary
protectors S270, S280 and S250.
- The terminals of the device have not been investigated for field wiring.
- The spacings provided between auxiliary switch S2-S/H and adjacent protector is 3 mm
through air or over surface. This requires that the auxiliary switch be at the same
polarity as the adjacent protector.
- The auxiliary switch S2-H is suitable for use with an adjacent protector of opposite
polarity.
- For use only in products where the acceptability of the combination is determined by CSA
International.
- Components supplementary protector accessory bus, Cat. Nos. KS 2/56, KS2/12, VB 45.32,
PSB3UL, PSB53UL, SZ-KS.
These accessories are copper buses intended to supply protectors from a single source.
Intended only for use with single pole protectors; except SZ-KS intended for use with
multi pole protectors.
Ratings:
KS 2/12 and KS 2/56 - 85A end supply (140A when center feed).
PSB3UL and PSB53UL - 40A for 10 mm2 and 63A for 16 mm2 in a 40C ambient. Max voltage
480V.
VB 45.32 - 110A end supply (140A when center feed).
SZ-KS: 40A for 10 mm² and 63A for 16 mm² in a 40C ambient. Max voltage 600V.
Notes:
- The busbar is for use with this manufacturer's supplementary protectors S250, S260, S270
and S280.
- PSB3UL, PSB53UL, SZ-KS have spacing of 6.4 mm through air and 9.5 mm over surface.
- Short circuit tests have not been conducted.
- For use only in products where the acceptability of the combination is determined by CSA
International.
- Component supplementary protector assembly, Shunt trip S2-A1 and S2-A2.
Ratings:
Voltage ratings S2-A1 - 12 to 60V ac-dc
S2-A2 - 110 to 415V ac
110 to 250V dc
Notes:
- These devices are intended for rail mounting and used in conjunction with supplementary
protector S280, S250 and S270.
- The terminals of the device have not been investigated for field wiring.
- For use only in products where the acceptability of the combination is determined by CSA
International.
- Component Supplementary Protectors, manual reset, thermo-magnetic trip units: Series
S200 followed with B, C, D, K or Z followed by a number between 0.5 and 63A may be
followed by additional suffixes. 1 to 4 pole.
- S200B rating 6 to 63A, and S200C, D, K and Z ratings 0.5 to 63A, 277V ac –1
phase, 480V ac – 3 phase or two pole breaking, Temperature range -25 Deg C
to 70 Deg C; Short Circuit Ratings: 6kA at
27V ac one pole and 480V ac
multipole;
10kA at 120V ac/60V dc one pole and 240V ac/125V dc multiple. May or may not
be provided with Auxiliary contacts (Types S2-H, S2-S/H, H01
H02
and
S2C-HxxR) and shunt trip
(S2-A1 and S2-A2).
- Auxiliary Switches
Model S2C-xxR with the ratings - 1A, 480V ac, 2A, 230V ac, 1A, 220V
dc, 1.5A, 110V dc, 2A, 60V dc and 4A, 24V dc.
Application Codes: See Table below.
Notes:
- Open type devices are Certified as components for use in assemblies where the
suitability of the combination is to be determined by the CSA International.
- These are intended for rail mounting.
- The terminals of the device have not been investigated for field wiring.
- These devices are not suitable for branch circuit protection.
- Short circuit tests were conducted without series fuse.
- The spacings from live parts of single devices to adjacent metal surface, and from the
outside pole of multipole devices to adjacent metal surface shall be evaluated in the end
product application.
- These protectors are designed for use in ambient of -25 Deg C to 70 Deg C. Calibration
tests were conducted in the ambient of 25 Deg C only. Verification of trip times to
published trip curve at ambients other than 25 Deg C need to be conducted.
- Component Supplementary Protectors, manual reset, thermo-magnetic trip units: Series
S200P followed with B, C, D, K or Z followed by a number between 0.2 and 25A may be
followed by additional suffixes. 1 to 4 pole.
Tripping Characteristics B begins with 6A, C, D and Z begins with 0.5A, and K begins with
0.2A; 277V ac - 1 phase; 277/480V ac - 3 phase, Temperature range - 25C to 55C; Limited
Short Circuit Withstand Ratings: 10kA at 277V ac one pole and 277/480V ac
multipole;
- Component Supplementary Protector Accessories for Series S200P:
- Auxiliary Contact S2C-H6R and Alarm (Signal)/Auxiliary Contact S2C-S/H6R
with the ratings - 1A, 480V ac; 2A, 277V ac; 1.5A, 125V dc; 2A, 60V dc and
4A, 24V dc.
- Auxiliary Switches
Model S2C-xxR with the ratings - 1A, 480V ac,
2A, 230V ac, 1A, 220V dc, 1.5A, 110V dc, 2A, 60V dc and 4A, 24V dc.
Application Codes: See Product Application Codes Table.
Notes:
- These are intended for rail mounting.
- The terminals of the device have not been investigated for field wiring.
- These devices are not suitable for branch circuit protection.
- Short circuit tests were conducted without series fuse.
- The spacings from live parts of single devices to adjacent metal surface, and from the
outside pole of multipole devices to adjacent metal surface shall be evaluated in the end
product application.
- These protectors are designed for use in ambient of -25 Deg C to 55 Deg C. Calibration
tests were conducted in the ambient of 25 Deg C only. Verification of trip times to
published trip curve at ambients other than 25 Deg C need to be conducted.
Product Application Codes:
| Series |
|
|
Application code |
|
TC |
OL |
SC |
| S260 |
TC2 |
OL0 |
U1, 6kA, 277V ac and 10kA 120V ac/60V dc (1-pole)
U1, 10kA, 240V ac and 125V dc (multipole) |
| S280 |
TC2 |
OL0 |
U1, 10kA, 277V ac (1-pole) for
devices 40A or less
U1, 6kA, 277V ac (1-pole) for devices greater 40A
U1, 10kA, 480V ac (Multipole) for devices 32A or less
U1, 6kA, 480V ac (Multipole) for devices greater 32A |
| S270 |
TC2 |
OL0 |
U1, 6kA, 277V ac (1-pole)
U1, 6kA, 480V ac (Multipole)
U1, 10kA, 120V ac or 60V dc (1-pole)
U1, 10kA, 240V ac or 125V dc (Multipole) |
| S200 |
TC2 |
OL0 |
U1, 6kA, 277V ac (1-pole)
U1, 6kA, 480V ac (Multipole)
U1, 10kA, 120V ac or 60V dc (1-pole)
U1, 10kA, 240V ac or 120V ac (Multipole) |
| S200P |
TC2 |
OL0 |
U1, 10kA, 277V ac
(1-pole)
U1, 10kA, 277/480V ac (Multipole) |
/ka