Certification Record

CUSTOMER CLASS FILE

ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000
Eppelheimer Strasse 82, SUPPLEMENTARY PROTECTORS-COMPONENT ACCEPTANCE PROGRAM
Heidelberg
Baden-Wurttemberg
69123
Germany Refer to Class Description for program details

These devices are one pole protectors that may be ganged together to form a multipole device (4 poles maximum). When ganged together a common trip lever is used between poles. The 1, 2, 3 and 4 following S26 or S28 stands for the number of poles. The letters in the catalogue number following the number of poles stands for the trip curve. The UC in the catalogue number means it has both ac and dc ratings. The last digits stand for the ampere rating.

RATINGS:

Current Ratings:

S280 Series the maximum rating is 63A

S260 has a minimum rating of 32A and a maximum rating of 63A.

S260-B has a minimum rating of 6A and a maximum rating of 63A.

S260-C has a minimum rating of 0.5A and a maximum rating of 63A.

S260-D has a minimum rating of 0.5A and a maximum rating of 63A.

Voltage Ratings:

S281 K, Z are rated 277V ac maximum.

S282 K, Z are rated 480V ac maximum.

S273, S263, S264, S283, S274 and S284 K, L, Z, UCK and UCZ are rated 480V ac maxium.

S281 UCK and UCZ are rated 277V ac, 250V dc maximum.

S282, S283, S284 UCK and UCZ are rated 400V ac, 500V dc maximum.

S261 are rated 277V ac, 60V dc.

S262, S263 and S264 are rated 480V ac, 125V dc (two poles in series).

Short Circuit Ratings -

S260 Series followed by D: 6kA/277V ac single pole 6kA/480V, 10kA rms symmetrical 120V ac, 60V dc, one pole, 240V ac, 125V dc multipole.

S280 Series followed by UCK or UCZ: all devices 4.5kA or dc. Devices rated 40A or less 6kA/240V. Devices rated greater than 40A - 5kA/277V ac for single pole 5kA/480V ac for multipole.

S280 Series followed by K or Z: single pole - devices rated 40A, or less - 10kA/277V ac, devices rated greater than 40A - 6kA/277V ac. Multipole: devices rated 32A or less - 10kA/480V ac, devices rated greater than 32A - 6kA, 480V ac.  
Application Codes:  See Product Application Codes Table.

Notes:

  1. These devices are intended to be rail mounted and should be mounted in a non-metallic enclosure or in a metallic enclosure having an insulator under the mounting wall.
  2. The terminals of the device have not been investigated for field wiring.
  3. These devices are not suitable for branch circuit protection.
  4. Short circuit Tests on the S280 protectors were conducted without series protection.
  5. For use only in products where the acceptability of the combination is determined by CSA International.
  6. Types S260 were subjected to Short Circuit Tests with series fuses rated 4 times the ampere rating of the protector. 6kA and 10kA short circuit tests with 277V ac and 480V ac on type S280 were conducted with series fuses rated 4 times the ampere rating of the protector.
  7. The spacings from live parts of single pole devices to adjacent metal surfaces, and from the outside poles of multipole devices to adjacent metal surface shall be evaluated in the end product application.
  8. Temperature Test on S260 was performed in an enclosure approx 157 mm by 59 mm by 68 mm.

These devices are one, two, three and four pole supplementary protectors provided with thermal magnetic trip units. Devices may or may not be provided with auxiliary switches. The 1, 2 or 3 following S26 or S27 stands for the number of poles. Poles with NA suffix have switch neutral pole with no trip.

RATINGS:

Current Ratings:

S270-K or Z ratings minimum 0.5A maximum 63A

Voltage Ratings:

One pole devices - 277V ac

Multipole devices - 480V ac (2 poles breaking

Short Circuit Ratings:

6kA rms symmetrical 277V ac, one pole, 480V ac multipole

10kA rms symmetrical 120V ac, 60V dc, one pole, 240V ac

125V dc multipole

Additional Ratings:

Temperature -25C to 25C (S260

Temperature -25C to 55C (S270

S280-K is suitable for across-the-line motor starting ac and may have hp ratings as indicated under "Markings".
Application Codes:  See Product Application Codes Table.

Notes:

  1. These devices are intended to be rail mounted.
  2. The terminals of the device have not been investigated for field wiring.
  3. These devices are not suitable for branch circuit protection.
  4. Short circuit tests on the following types of protectors were conducted without series protection. S270-K rated 0.5-40A and 110V dc or 240V ac (multipole); or 60V dc (1 pole).
  5. The spacing provided between adjacent terminals on multipole devices when the devices are used in pollution degree 2 environments and overvoltage category 3 or better.
  6. The spacings from live parts of single pole devices to adjacent metal surfaces, and from the outside poles of multipole devices to adjacent metal surface shall be evaluated in the end product application.
  7. The temperature test for devices suitable for 25C ambient was performed in an enclosure measuring approx 157 mm by 59 mm by 68 mm.
  8. Short circuit tests for 10kA rating were conducted without series protection.
  9. For use only in products where the acceptability of the combination is determined by CSA International.

These devices are auxiliary contacts intended for use with this manufacturer's supplementary protectors, S280, S270 and S250. Auxiliary contacts operate off the protector main contact mechanism. The signal contact on the S2-S/H operates off the protector trip mechanism.

Ratings:

S2-S/H .5A, 250V dc 2A, 415V ac
1A, 110V dc 6A, 240V ac
4A, 24V dc
S2H and S3-4 2A, 60V dc 6A, 240V ac

Notes:

  1. These devices are intended for rail mounting and used in conjunction with supplementary protectors S270, S280 and S250.
  2. The terminals of the device have not been investigated for field wiring.
  3. The spacings provided between auxiliary switch S2-S/H and adjacent protector is 3 mm through air or over surface. This requires that the auxiliary switch be at the same polarity as the adjacent protector.
  4. The auxiliary switch S2-H is suitable for use with an adjacent protector of opposite polarity.
  5. For use only in products where the acceptability of the combination is determined by CSA International.

These accessories are copper buses intended to supply protectors from a single source. Intended only for use with single pole protectors; except SZ-KS intended for use with multi pole protectors.

Ratings:

KS 2/12 and KS 2/56 - 85A end supply (140A when center feed).

PSB3UL and PSB53UL - 40A for 10 mm2 and 63A for 16 mm2 in a 40C ambient. Max voltage 480V.

VB 45.32 - 110A end supply (140A when center feed).

SZ-KS: 40A for 10 mm² and 63A for 16 mm² in a 40C ambient.  Max voltage 600V.

Notes:

  1. The busbar is for use with this manufacturer's supplementary protectors S250, S260, S270 and S280.
  2. PSB3UL, PSB53UL, SZ-KS have spacing of 6.4 mm through air and 9.5 mm over surface.
  3. Short circuit tests have not been conducted.
  4. For use only in products where the acceptability of the combination is determined by CSA International.

Ratings:

Voltage ratings S2-A1 - 12 to 60V ac-dc

S2-A2 - 110 to 415V ac

110 to 250V dc

Notes:

  1. These devices are intended for rail mounting and used in conjunction with supplementary protector S280, S250 and S270.
  2. The terminals of the device have not been investigated for field wiring.
  3. For use only in products where the acceptability of the combination is determined by CSA International.


Application Codes:  See Table below.

Notes:

  1. Open type devices are Certified as components for use in assemblies where the suitability of the combination is to be determined by the CSA International.
  2. These are intended for rail mounting.
  3. The terminals of the device have not been investigated for field wiring.
  4. These devices are not suitable for branch circuit protection.
  5. Short circuit tests were conducted without series fuse.
  6. The spacings from live parts of single devices to adjacent metal surface, and from the outside pole of multipole devices to adjacent metal surface shall be evaluated in the end product application.
  7. These protectors are designed for use in ambient of -25 Deg C to 70 Deg C. Calibration tests were conducted in the ambient of 25 Deg C only. Verification of trip times to published trip curve at ambients other than 25 Deg C need to be conducted.

Notes:

  1. These are intended for rail mounting.
  2. The terminals of the device have not been investigated for field wiring.
  3. These devices are not suitable for branch circuit protection.
  4. Short circuit tests were conducted without series fuse.
  5. The spacings from live parts of single devices to adjacent metal surface, and from the outside pole of multipole devices to adjacent metal surface shall be evaluated in the end product application.
  6. These protectors are designed for use in ambient of -25 Deg C to 55 Deg C. Calibration tests were conducted in the ambient of 25 Deg C only. Verification of trip times to published trip curve at ambients other than 25 Deg C need to be conducted.

Product Application Codes:

Series Application code
TC OL SC
S260 TC2 OL0 U1, 6kA, 277V ac and 10kA 120V ac/60V dc (1-pole)
U1, 10kA, 240V ac and 125V dc (multipole)
S280 TC2 OL0 U1, 10kA, 277V ac (1-pole) for devices 40A or less
U1, 6kA, 277V ac (1-pole) for devices greater 40A
U1, 10kA, 480V ac (Multipole) for devices 32A or less
U1, 6kA, 480V ac (Multipole) for devices greater 32A
S270 TC2 OL0 U1, 6kA, 277V ac (1-pole)
U1, 6kA, 480V ac (Multipole)
U1, 10kA, 120V ac or 60V dc (1-pole)
U1, 10kA, 240V ac or 125V dc (Multipole)
S200 TC2 OL0 U1, 6kA, 277V ac (1-pole)
U1, 6kA, 480V ac (Multipole)
U1, 10kA, 120V ac or 60V dc (1-pole)
U1, 10kA, 240V ac or 120V ac (Multipole)
S200P TC2 OL0 U1, 10kA, 277V ac (1-pole) 
U1, 10kA, 277/480V ac (Multipole) 


/ka